Consultazione dati aggregati - Esito Aggregazione N° 11132
 
Selected Parameters
MeasureDips
Start date08/11/2021
Stop date14/11/2021
RegionLOMBARDIA
Network extensionAll
Rated voltageAll
Neutral typeAll
AggregabilityPrimary Substations
MacroareaAll

Total number of aggregated points of measure: 65
Equivalent points of measure within the selected period : 18,0
Total weeks: 1

Voltage dips within the selected interval (CEI EN 50160)
Residual V. [%]Dips NumberAvg. duration [s]
80…9010,080
70…8040,108
40…7060,110
5…400-
1…50-


Avg. number of voltage dips for equivalent point of measure within the selected interval (CEI EN 50160)
  Voltage dips duration
   20-200 ms200-500 ms500-1000 ms1-5 s5-60 s
Residual V. [%]80…900,10,00,00,00,0
70…800,20,00,00,00,0
40…700,30,00,00,00,0
5…400,00,00,00,00,0
1…50,00,00,00,00,0
Ntot=0,60   N2a=0,30   N3b=0,00




95% of aggregated points of measure have a number of voltage dips less or equal than value indicated in the table (95° Percentile CEI EN 50160)
  Voltage dips duration
   20-200 ms200-500 ms500-1000 ms1-5 s5-60 s
Residual V. [%]80…9000000
70…8010000
40…7020000
5…4000000
1…500000

Voltage dips Count Percentiles of All origin
Dips Type95°75°50°25°
N2a (*) 20000
N3b (**)00000
All20000
(*)  N2a: voltage dips below the class 2 immunity curve
(**) N3b: voltage dips below the class 3 immunity curve


Voltage dips of MV origin within the selected interval (CEI EN 50160)
Residual V. [%]Dips NumberAvg. duration [s]
80…9010,080
70…8040,108
40…7060,110
5…400-
1…50-


Avg. number of voltage dips of MV origin for equivalent point of measure within the selected interval (CEI EN 50160)
  Voltage dips duration
   20-200 ms200-500 ms500-1000 ms1-5 s5-60 s
Residual V. [%]80…900,10,00,00,00,0
70…800,20,00,00,00,0
40…700,30,00,00,00,0
5…400,00,00,00,00,0
1…50,00,00,00,00,0
Ntot=0,60   N2a=0,30   N3b=0,00




95% of aggregated points of measure have a number of voltage dips of MV origin less or equal than value indicated in the table (95° Percentile CEI EN 50160)
  Voltage dips duration
   20-200 ms200-500 ms500-1000 ms1-5 s5-60 s
Residual V. [%]80…9000000
70…8010000
40…7020000
5…4000000
1…500000

Voltage dips Count Percentiles of MV origin
Dips Type95°75°50°25°
N2a (*) 20000
N3b (**)00000
All20000
(*)  N2a: voltage dips below the class 2 immunity curve
(**) N3b: voltage dips below the class 3 immunity curve


HV voltage dips within the selected interval (CEI EN 50160)
Residual V. [%]Dips NumberAvg. duration [s]
80…900-
70…800-
40…700-
5…400-
1…50-


Avg. number of voltage dips of HV origin for equivalent point of measure within the selected interval (CEI EN 50160)
  Voltage dips duration
   20-200 ms200-500 ms500-1000 ms1-5 s5-60 s
Residual V. [%]80…900,00,00,00,00,0
70…800,00,00,00,00,0
40…700,00,00,00,00,0
5…400,00,00,00,00,0
1…50,00,00,00,00,0
Ntot=0,00   N2a=0,00   N3b=0,00




95% of aggregated points of measure have a number of HV dips less or equal than value indicated in the table (95° Percentile CEI EN 50160)
  Voltage dips duration
   20-200 ms200-500 ms500-1000 ms1-5 s5-60 s
Residual V. [%]80…9000000
70…8000000
40…7000000
5…4000000
1…500000

Voltage dips Count Percentiles of HV origin
Dips Type95°75°50°25°
N2a (*) 00000
N3b (**)00000
All00000
(*)  N2a: voltage dips below the class 2 immunity curve
(**) N3b: voltage dips below the class 3 immunity curve